User guide

Strobix user guide

How to load measurement data, review coverage volumes and export the results.

Version: pre-release, 2026-11-12

Getting started

Strobix analyses photometric measurement data (CSV files) for visual alarm devices and shows the EN 54-23 coverage volume. The usual order of work is:

  1. Choose File > New Project and fill in the project.
  2. Choose Edit > Add Configuration... for the device you measured.
  3. Load the configuration’s CSV measurement file.
  4. Review the Point Cloud Raw and Coverage Volume tabs.
  5. Export the table or the 3D views, and save the project.

The window. The left panel shows the project name and VAD type, the Configurations: tree, a Comments: box and the Data file: line with the Browse... and Load buttons. The right panel has these tabs: Raw Data, Averaged Data, Point Cloud Raw, Coverage Volume and Table Export. Two more tabs, Configuration and Raw File Info, are reserved for a later version and are empty today.

Menus. File: New Project, Open Project..., Save Project, Save Project As..., Close Project, Exit. Edit: Add Configuration..., Delete Configuration, Rename/Modify..., Duplicate Configuration. Options: Preferences..., License.... Help: About....

Strobix follows the EN 54-23:2010 method as implemented. It does not certify a device, and checking the results remains your responsibility.

Installing

Strobix runs on Windows 10 version 1809 or later and on Windows 11. The download page explains how to install it, what the Windows security warning means and how to uninstall.

Licence

You can try Strobix for 14 days with one licence. After that you need a licence, which you can buy on the pricing page. One licence covers one computer.

Enter your licence key in the licence dialog, which you open from Options > License.... Strobix checks the licence online each time it starts. If it cannot reach the internet it keeps working for up to 7 days after the last successful check. After that the licence dialog blocks the program until a check succeeds.

Before you uninstall Strobix or move it to another computer, deactivate the licence in the licence dialog, so that its place is freed for the other computer.

Projects

A project holds your configurations, comments and the paths of your data files, and is saved as a .vadprj file.

  • File > New Project opens the New Project dialog with Project title: and VAD type: (Type A, Type B or Other).
  • File > Open Project... opens a file of type “VAD Project Files (*.vadprj)”. Only one project can be open at a time; opening a second shows Project Already Open.
  • Save Project and Save Project As... write the file. A [*] in the window title marks unsaved changes.
  • Opening a legacy MATLAB project converts it: Strobix saves a _converted.vadprj copy next to the original and leaves the original untouched.

Configurations

A configuration stands for one measured device. Use Edit > Add Configuration... (or right-click the tree) to open the Add VAD Configuration dialog with these fields:

  • Configuration name:
  • Configuration type: Coverage Volume, Reproducibility or Other
  • Sample number:

Right-click a configuration in the tree for: Add Configuration..., Duplicate, Rename/Modify..., Delete and Load CSV File.... The same actions are in the Edit menu.

Loading measurement data

Select a configuration, then either choose Browse... and Load next to Data file:, or drag a CSV file and drop it onto the configuration tree. Strobix reads the measurement rows and detects the device type from the information in the file. If a data file can no longer be found, its path shows in red and the configuration is marked in the tree.

Raw Data and Averaged Data

The Raw Data tab shows the rows of the file. The Averaged Data tab shows the averaged measurements and keeps only the rows whose “Coverage distance test” is Pass.

Point Cloud Raw

This tab shows the measurement points in 3D. The toolbar has:

  • Show Best/Worst, a box that marks the best and worst points in green and red (off by default);
  • Lock Scale, with a Scale value field;
  • Export 3D, which opens Export 3D View where you choose Save to File... (a PNG image) or Copy to Clipboard.

Right-click the view for Save as PNG... and Copy to Clipboard.

Coverage Volume

This tab shows the coverage volume in 3D with a results table (columns “X value” and “Y value”). It has the same Lock Scale and Export 3D controls as Point Cloud Raw.

  • Ceiling devices: the worst cross-section at 3, 6 and 9 m below the device.
  • Wall devices: the range from 2.4 m to 30 m.
  • Processed As: Ceiling, Wall, Open or Unknown. Strobix detects the device type from the file; if you choose a different one, an orange warning shows “Auto-detected: X. Processing as: Y.”.
  • X: and Compute add a result for a value of your own to the table.
  • Open class: EN 54-23 does not define coverage volume for open class, so the controls are disabled and a tooltip says so.

Table Export

Tick the columns of the averaged data you want; the preview updates as you tick. Choose Export... to save an Excel file (.xlsx) or a CSV file, picking the type in the save dialog. Choose Copy to Clipboard to copy the table as tab-separated text, ready to paste into a spreadsheet.

Preferences

Options > Preferences... currently says “Preferences will be available in a future release.” Your settings are stored in a file called preferences.toml in %APPDATA%\MecaFrog\Strobix.

Updates

Each time it starts, Strobix checks whether a newer version has been published. If there is one, an Update Available notice shows the new version and the address of the release page. Strobix never downloads or installs an update by itself. See the privacy page for what the check sends.

Help

Help > About... shows the version, the publisher and the website and support links. For help, email info@mecafrog.com.